GM-4000
The GM-4000 is a microprocessor-based four-channel controller with four independent LCD displays. This economical unit is designed for ease of installation and operation.
General Description
Field adjustable setpoints for each channel allow the operator to easily set or adjust Warning (low alarm) and Alarm (high alarm) trip levels at the main control panel.
Each channel of the controller has a three digit alphanumeric Status LCD display of gas concentration, a Warning LED, Alarm LED, and Fault LED for complete "at a glance" system status.
The GM-4000 is equipped with a de-energized common Warning relay, a de-energized common Alarm relay, an energized common Fault relay, and eight discrete relays (Warning and Alarm for each channel). The eight discrete relays are field selected to function as energized or de-energized and latching or non-latching.
Two front panel touch-pad switches (Reset Alarm and Lamp Test) are used as control switches to acknowledge alarms and as a general system test. They are also used to calibrate the LCD (if necessary) and to adjust the alarm setpoints when in calibration mode.
Designed for easy installation, the GM-4000 is housed in a slim wall mounted, hinged swing-down door enclosure. All of the wiring terminals are located inside, opposite the applicable port for conduit fitting. The RFI / EMI protected enclosure is powder-coated steel.
Specifications
| Power | |
|---|---|
| Electrical Supply | Field selectable for AC (115 or 230) or DC (24 VDC)50/60 Hz; 24 VDC, 1.5 amps NOTE: If any sensor has a current draw of more than 250 mA, an external power supply is required. |
| Backup | Rechargeable 12V battery kit supplies approximately 3 hours in normal operation dependant on the draw of each sensor connected. |
| Fuse Rating | 250 mA @ 30 watts |
| Fuse Type | Resettable (auto) |
| Environmental | |
| Operating Temperature | -4 to +122° F |
| Relative Humidity | 5 to 99% (non-condensing) |
| Altitude | Up to 6,500 ft |
| Enclosure Rating | NEMA 12 |
| Physical | |
| Dimensions | 2.4" x 13.0" x 9.5" |
| Weight | 4.85 lb. |
| Enclosure | Enameled Steel RFI / EMI protected |
| Wire Termination | Screw type terminal block |
| Wiring ports | Seven 3/4" NPT ports |
| Mounting | Wall mounted - equipped with hanging slots and hinged door |
| Alarms | |
| Type | Two setpoints, user programmable, with simple rotary switch |
| Audible | 85 dB buzzer |
| Relay Outputs | SPDT Relays Rated Load: 10 amps @ 115 VAC; 8 amps @ 230 VAC Operation Load (Max): 250 VAC; 125 VDC |
| Alarm Relays |
|
| Display Panel | |
| Backlit LCDs | Four independent 3-digit alphanumeric status displays, %LEL, PPM, or O2% by vol. readouts (field selectable) |
| LED Indicators | Alarms: Low (red), High (red), and Fault (amber) Power: On, AC or DC (green) Gas: Concentration Icon - ppm, %O2 and %LEL |
| Controls | Two large pushbutton controls Reset Alarm - acknowledge, peak exposures Lamp Test - audible / visual alarm test Alarm setpoints: Simple up / down buttons |
| Ratings / Certifications | |
| Area Classification | ANSI/ISA S82.01; CAN/CSA C22.2 No. 1010-1 |
Specifications are subject to change without notice.
Downloads
Key Features
- Continuous, alphanumeric "status" LCD for each channel
- Easy installation
- Local 85 dB audible alarm
- Field programmable alarm levels
- Simple operation
- Mix, match or change the gases monitored
- Three common 10 amp relay outputs: Warning, Alarm and Fault
- Eight discrete 10 amp relay outputs: 2 per channel for warning and alarm
- Records and displays Peak (Max) gas concentration for each channel