GM-1 Analog Output Board
Manning Systems GM-1 Single Channel Readout / Alarm Unit has audible / visual indications of gas concentration, as well as three (3) relay outputs as a standard feature. When an application requires that the 4/20 mA signal also be monitored, the optional GM-1-AOB provides a means to send that sensor signal directly to a PLC or other monitoring device that will input a 4/20 mA signal.
The GM-1-AOB Analog Output Board provides an isolated, 2-wire, 4/20 mA output signal. The Analog Output Board requires the customer's monitoring equipment to provide a 12 to 24 VCD supply voltage applied at the "+24" terminal and returns 4/20 mA at the "SIG" terminal. If the signal from the sensor is lost, the GM-1-AOB returns a 0.5 mA signal. The output operates as a two wire, loop powered device.
For larger applications, the Manning Systems GM-10 and GM-4 Multi-channel Readout / Alarm Systems also have optional 4/20 Analog Output Boards available.
Specifications
| Supply Voltage, Vs: | +12 to +24 VDC nominal, 30 VDC maximum |
|---|---|
| Supply Current, Is: | 0.5 to 20 mA, reverse protected |
| Nominal Load Resistance: | 100 Ohms |
| Maximum Load Including Cable: | Vs = 12 volts 200 Ohms Vs = 15 volts 300 Ohms Vs = 20 volts 500 Ohms Vs = 24 volts 600 Ohms |
| Connections: | Phoenix 2 pin vertical socket, mating plug supplied |