GM-10 Analog Output Board
In addition to the standard relay outputs (total of four) on a GM-10, the analog output board provides an isolated 2-wire, 4/20 mA output for each of the GM-10 channels (total of ten).
Space is available in the GM-10 to further add to its output capability by the addition of a ten-channel relay board operating in combination with the Model GM-10-AOB and standard common relay outputs.
These options can be ordered with the original GM-10 unit or easily added later in the field if individual annunciation is required to enhance the function of safety equipment.
Specifications
| Supply Voltage, Vs | +12 to +24 VDC nominal, 30 VDC maximum |
|---|---|
| Supply Current, Is: | 0.5 to 20 mA, reverse protected |
| Nominal Load Resistance: | 100 Ohms |
| Maximum Load Including Cable: | Vs = 12v 200 Ohms |
| Connections: | Phoenix 2 pin vertical socket, mating plug supplied |
For further details, please refer to the GM-10 Installation and Operation Manual.